Installation
6
24
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
Buderus • http://www.buderus.net
We reserve the right to make any changes due to technical modifications!
Fig. 23
Horizontal parallel venting system (sealed
combustion)
EXHAUST
3" (80 mm)
min. 12"
INTAKE
3" (80 mm)
12" (300 mm)
minimum
12"
(300 mm)
minimum
12"
(300 mm)
minimum
12"
(300 mm)
minimum
12"
(300 mm)
minimum
Fig. 24
Vertical venting system (room air only)
INTAKE
EXHAUST
10"- 0" MIN
(250 mm - 0 mm MIN)
12" (300 mm) OVER MAXIMUM
SNOW LEVEL OR 24" (600 mm)
WHICHEVER IS
GREATER
3" (80 mm)
Fig. 25
Vertical exhaust and horizontal intake venting system
(sealed combustion)
INTAKE
3" (80 mm)
EXHAUST
3" (80 mm)
10"- 0" MIN
(250 mm - 0 mm MIN)
12" (300 mm) OVER MAXIMUM
SNOW LEVEL OR 24" (600 mm)
WHICHEVER IS
GREATER
Fig. 26
Horizontal venting system (sealed combustion)
INTAKE
EXHAUST
3" (80 mm)
3" (80 mm)