Start-up procedure
9
38
Installation instructions Logamax plus GB142-24/30/45/60 • version 10/2007
Buderus • http://www.buderus.net
We reserve the right to make any changes due to technical modifications!
z
Push against the drawer (fig. 40) to close the control
panel.
9.13 Testing the Ignition Safety shut off
device
z
Switch off the heating system using the main switch.
z
Disconnect the plug and socket connection of the moni-
toring cable.
z
Switch on the heating system using the main switch.
z
Press the "Chimney Sweep"
d
button and hold it (for
approx. two seconds), until the display shows the
decimal point.
z
Check if the boiler does one start-up attempt and three
restart attampts.
After each start-up attempt the boiler will signal a start-up
failure. A "
6A
" code can be seen in the display.
After the last start-up attempt, the boiler will lock out. The
"
6A
" code is blinking in the display.
z
Connect the plug and socket connection of the moni-
toring cable.
z
Press the reset button.
z
Check if the boiler starts-up.
z
Press the "Chimney Sweep" button return to normal
operating conditions.
9.14 Installing the casing
z
Install the casing and close the latches (fig. 41).
Do not lift the casing by the latches!
z
Lock the latches using the radiator key.
9.15 Informing the owner, handing over the
technical documents
z
Show the owner how the heating system works and how
the boiler can be operated. Hand over the technical
documents.