18
#
Menu Item
Function
Default
Value
8
PUMP 2 COUNT
The cumulative number of pump starts for pump 2.
This is a cumulative counter, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-
9
PUMP 2 HOURS
The cumulative run time in hours for pump 2.
This is a cumulative timer, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-
10
ALARM COUNT
The cumulative number of all alarm incidents.
This is a cumulative counter, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-
11
POWER
INTERRUPTED
The cumulative number of power interruptions (i.e. controller
turned off/ power cut).
This is a cumulative counter, the value of which cannot be
modified. If using the engineer’s code, the counter can be reset
to zero by holding the (MUTE) button.
-
12
PULSE
When enabled, if a pump has been inactive for 60 days, it will
start and run for 2 seconds.
This is to prevent the pumps from seizing.
NO
13
EXCESSIVE
START
When enabled, if there are more than 3 individual pump runs
within an 8 hour period, the unit will register an <EXCESSIVE
DEMAND> alarm.
Enabling this option may cause false alarms on some systems.
NO
14
SERVICE
When enabled, a service reminder will be displayed after 12
months from when the option was enabled.
To reset the service reminder, set the value to ‘NO’ and exit the
menu. Then, re-enter the menu and set the value to ‘YES’ again.
NO
15
FILL SYSTEM
When enabled, the <LOW PRESSURE> and <FLOOD LIMIT>
alarms will be disabled, and pump 1 will run continuously for up
to 24 hours until the cold fill pressure has been reached.
Once the cold fill pressure has been reached, this option will
automatically be deactivated, and the low pressure alarm and
flood limit will be reactivated.
This function is used to fill a system that is empty or at low
pressure.
Care must be taken using this option as the flood limit alarm is
disabled, increasing the risk of flooding.
This option cannot be enabled on Mini pressurisation units.
NO
If using the customer code, the menu will end at this point. After pressing (SET) once
more, the controller will display “SAVING...” and return to normal operating mode. If
using the engineer’s code, additional menu items will be displayed.
The following settings are all pre-programmed in the factory and should not need to
be modified on site. If these settings appear to have been reset, the most likely cause
is a power spike. If this problem persists, a power filter may be required.
Содержание AX1-2.5E
Страница 33: ...33 Wiring Diagram ...
Страница 34: ...34 Service Log This service log should be completed by the service engineer after each annual service ...
Страница 35: ...35 ...
Страница 41: ...41 Notes ...
Страница 42: ...42 Notes ...
Страница 43: ...43 Notes ...
Страница 44: ...44 Notes BOSS Pressurisation O M Manual Version 8 February 2014 ...