Equipment Overview
The function of this pressurisation unit is to provide a means of automated water top-up to sealed
heating and cooling systems. The equipment is designed to provide periodic water top-up to
compensate for minor losses in system pressure (e.g. slow leaks, air venting, etc.).
This equipment is not designed to cope with sudden losses of system pressure (e.g.
manual draining) or major water losses (e.g. large leaks). The equipment is also not
intended to be used for water boosting applications.
Principal of Operation
The following schematic shows the internal arrangement of a pressurisation unit:
The pressurisation unit is fitted with a break tank (1) which is filled from the mains water supply (2)
via a float operated valve (3). The break tank is fitted with an overflow (4) in case the break tank
overfills, and a weir overflow (5) in case the primary overflow fails.
The pressurisation unit is connected into the heating system (6) via an isolation valve (7).
The pressure sensor (8) monitors the system pressure.
If the pressure sensor detects a drop in pressure, the pump (9a) will pump water from the break tank
into the system. Once the required pressure has been reached, the pump will stop.
On twin pump models, a second pump (9b) is provided. The two pumps will run in a duty/standby
configuration (i.e. the active pump will alternate with each pump start).
The pump(s) are fitted with non-return valves (10a, 10b) to prevent backflow.
A drain valve (11) is provided for draining down the unit and for commissioning purposes.
Содержание AX1-2.5E
Страница 33: ...33 Wiring Diagram ...
Страница 34: ...34 Service Log This service log should be completed by the service engineer after each annual service ...
Страница 35: ...35 ...
Страница 41: ...41 Notes ...
Страница 42: ...42 Notes ...
Страница 43: ...43 Notes ...
Страница 44: ...44 Notes BOSS Pressurisation O M Manual Version 8 February 2014 ...