The supply voltage must comply with overvolt‐
age category II! Otherwise the integrated pow‐
er supply unit might be destroyed.
CAUTION
Use an isolating transformer to generate the AC230/115 V, see
230 V voltage connection via isolating transformer" on page 44
.
The AC 230/115 V connection occurs via a 3-pin inlet connector for AC con‐
nectors on the connector panel. The maximum line cross-section for the con‐
nected lines is 1.5 mm
2
.
X20
Belegung
PE
N1
U2
PE
Assignment
PE
Fig.7-24:
AC 230/115 V connection, X20, pin connection
Parameter
Value
Rated voltage
AC 85 V... AC 264 V
auto range
Current consumption for U
N
= AC 230 V
0.7 A
Current consumption for U
N
= AC 115 V
1.4 A
Inrush current for U
N
= AC 230 V
30 A cold start 25 °C
Inrush current for U
N
= AC 115 V
15 A cold start 25 °C
Input fuse
1.6 A (5×20)
Fig.7-25:
Technical data AC 230/115 V connection
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Bosch Rexroth AG
43/81
Connections
Содержание Rexroth lndraControl VPB 40.1
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 6: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC IV 81 ...
Страница 20: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 18 81 ...
Страница 48: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 46 81 ...
Страница 72: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 70 81 ...
Страница 78: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 76 81 ...
Страница 80: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 78 81 ...
Страница 83: ...Notes DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC Bosch Rexroth AG 81 81 ...