Enable Temp Control: active
●
Enable Fan Control: active
●
Enable Voltage Control: active
●
Disable UPS: inactive
●
No Powerdown on Shortbreak: active
●
Execute Command File: inactive
System Health
This tab indicates the current measured values of the internal operating vol‐
tages, the battery voltage, the system temperature and the status of the fan
function.
Fig.9-6:
System Health tab
The value of the battery voltage (Battery Voltage) is only updated after a battery
test. The battery test occurs automatically after a system start and then every
12 hours or after having pressed the Test Battery button.
●
The LED flashes red, if the value of the battery voltage, which was meas‐
ured under load, is too low.
●
The LED flashes green, if the battery pack is ready for operation.
Possible damages to the VPB 40.1 and the
connected machines if the UPS functionality is
not guaranteed anymore caused by excessive
battery tests.
NOTICE
Excessive battery tests discharge the battery pack. Do not perform more than
five battery tests within a 24 hour period.
The following applies to the fan monitoring (Fan Speed):
Bosch Rexroth AG
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
66/81
Software
Содержание Rexroth lndraControl VPB 40.1
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 6: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC IV 81 ...
Страница 20: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 18 81 ...
Страница 48: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 46 81 ...
Страница 72: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 70 81 ...
Страница 78: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 76 81 ...
Страница 80: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 78 81 ...
Страница 83: ...Notes DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC Bosch Rexroth AG 81 81 ...