If this check box is activated, the existing housing fans and CPU fans are moni‐
tored. In error case a corresponding message is indicated and is sent to the
whole system.
Enable Voltage Control:
If this checkbox is activated, the internal supply voltages are monitored. In error
case a corresponding message is indicated and is sent to the whole system.
No Powerdown on Shortbreak:
If this checkbox is activated, interruptions of the supply voltage up to 5 seconds
are permissible without influencing the operation. Only for voltage breakdowns
> 5 seconds the UPS logic is started and the shutdown of the system is initiated.
UPS Off, Disable UPS:
The function UPS Off, Disable UPS deactivates the UPS monitoring and the
delay, when the power supply unit is switched off:
●
If a voltage breakdown occurs, the PC switches immediately off.
●
After a conventional shutdown of the system, there is no waiting time of
approximately 60 seconds until the power supply unit switches off.
This function shortens the waiting time during commissioning and software in‐
stallation. However, this checkbox must not be activated in the normal mode!
Data loss if voltage loss occurs during activa‐
ted "UPS Off, Disable UPS" checkbox! Dam‐
ages to connected machines and to VPB
40.1 are possible if the VPB 40.1 switches off
immediately while the "UPS OFF" checkbox is
activated.
CAUTION
If this checkbox is activated, a proper system shutdown is no longer possible
during a voltage breakdown. The device switches off immediately! Therefore,
this checkbox must not be activated during normal operation!
Command
In the Command group an executable program (*.exe; *.bat) can be entered
and activated, which should be started and executed after the initialization of
the shutdown. This is always reasonable, if applications which do not respond
to the system messages, have to be backuped or stopped. For this, corre‐
sponding clearing and terminating programs can be entered and activated. If
several programs are to be executed or if the programs feature transfer pa‐
rameters, they have to be combined and entered in a batch file.
Possible malfunctions if request parameters
are transmitted.
NOTICE
The entry must not contain any request parameters and the specified program
must not start any shutdown!
Default
If the Default button is activated, all settings are reset to their Default values.
These default values are:
●
COM Port: COM4
●
Shutdown Delay Time: 30 seconds
●
Enable Startup Battery Test: active
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Bosch Rexroth AG
65/81
Software
Содержание Rexroth lndraControl VPB 40.1
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 6: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC IV 81 ...
Страница 20: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 18 81 ...
Страница 48: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 46 81 ...
Страница 72: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 70 81 ...
Страница 78: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 76 81 ...
Страница 80: ...Bosch Rexroth AG DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC 78 81 ...
Страница 83: ...Notes DOK SUPPL VPB 40 1 PR02 EN P Rexroth IndraControl VPB 40 1 Control Cabinet PC Bosch Rexroth AG 81 81 ...