Breakpoints cannot be set in this state because the analyzer mode is not active
in the NC analyzer. If you try to switch to analyzer mode, an error message is
shown:
Start NC analyzer
●
Starting the NC analyzer
●
Select the channel with the faulty program
–
The location at which the NC program was stopped due to an error
is shown in the "Program" window of the NC analyzer
–
The start structure (in case of a possible subroutine stacking in the
NC program) is shown in the "Stack" window
–
Subroutines can be selected in the "Stack" window and shown using
the F-key <F5> ("Go to start") in the "Program" window to analyze
their program variables
Often the error can be found with this information alone.
However, the least benefit is that the faulty program section is known,
which can then be analyzed in the analyzer mode.
●
Clear the error source
Test the program
Before carrying out any further machine editing, you should once again test the
program for freedom from errors. The NC analyzer can be a very helpful tool
here as well, as the information (values) of the variables used can be opened
at any time during the program execution.
Messages of the NC Analyzer
System and user messages of the NC analyzer are shown in popup windows
with error text classification.
Type
Class
Description
System error_
- Error
- Critical error
Critical system error*) ->Critical
Error
Internal error rendering all further operation of the control impossible.
The NC analyzer closes automatically after confirmation.
Slight system error*) ->Critical
error
Internal error rendering a part section of the control non-functional. The
user can decide whether to continue working with the NC analyzer.
Warning
System warning
Warning from a part section of the NC analyzer, such as Failed to load
configuration data.
- Of the user pro‐
gram
Information:
- General
System information
Such as Number of breakpoints exceeded.
Programmed notice
Programmed notice from the NC program:
●
(MSG)
PRN’(0,….)
Entry error
Operating error
Such as Variable value invalid
*)
In case of system errors, service must be notified as well.
Fig.11-6:
Error classes NC analyzer
User Reactions to Errors and Messages
The following steps are possible in case of messages, warnings and "slight"
system errors:
●
Discard messages or errors as long as it is still possible to work with the
NC analyzer or as long as information on error clearance is provided.
●
Restart the surface
●
Contact service
186/233 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraMotion MTX 09VRS | Application Description
Extended Functionality
Содержание Rexroth IndraMotion MTX 09VRS
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 12: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 16: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 86: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 122: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 234: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 238: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 246: ...Bosch Rexroth AG Electric Drives and Controls Rexroth IndraMotion MTX 09VRS Application Description ...
Страница 247: ...Notes Application Description Rexroth IndraMotion MTX 09VRS Electric Drives and Controls Bosch Rexroth AG ...