Secure built-in devices from penetrating foreign objects and water, as
well as from direct contact, by providing an external housing, for exam‐
ple a control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injury
by electric shock!
●
Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipment
grounding conductor at the grounding points.
●
Connect the equipment grounding conductor of the components of the
electric drive and control system permanently to the main power supply
at all times. The leakage current is greater than 3.5 mA.
●
Establish an equipment grounding connection with a minimum cross
section according to the table below. With an outer conductor cross sec‐
tion smaller than 10 mm
2
(8 AWG), the alternative connection of two
equipment grounding conductors is allowed, each having the same
cross section as the outer conductors.
Cross section outer con‐
ductor
Minimum cross section equipment grounding conductor
Leakage current ≥ 3.5 mA
1 equipment grounding
conductor
2 equipment grounding
conductors
1.5 mm
2
(16 AWG)
10 mm
2
(8 AWG)
2 × 1.5 mm
2
(16 AWG)
2.5 mm
2
(14 AWG)
2 × 2.5 mm
2
(14 AWG)
4 mm
2
(12 AWG)
2 × 4 mm
2
(12 AWG)
6 mm
2
(10 AWG)
2 × 6 mm
2
(10 AWG)
10 mm
2
(8 AWG)
-
16 mm
2
(6 AWG)
16 mm
2
(6 AWG)
-
25 mm
2
(4 AWG)
-
35 mm
2
(2 AWG)
-
50 mm
2
(1/0 AWG)
25 mm
2
(4 AWG)
-
70 mm
2
(2/0 AWG)
35 mm
2
(2 AWG)
-
...
...
...
Tab. 3-1:
Minimum cross section of the equipment grounding connection
3.3.2
Protective extra-low voltage as protection against electric shock
Protective extra-low voltage is used to allow connecting devices with basic in‐
sulation to extra-low voltage circuits.
On components of an electric drive and control system provided by Rexroth,
all connections and terminals with voltages up to 50 volts are PELV ("Protec‐
tive Extra-Low Voltage") systems. It is allowed to connect devices equipped
with basic insulation (such as programming devices, PCs, notebooks, display
units) to these connections.
DOK-INDRV*-HCS01******-PR05-EN-P
Bosch Rexroth AG
35/341
Rexroth IndraDrive CsDrive Systems with HCS01
Safety instructions for electric drives and controls
Содержание Rexroth IndraDrive CsDrive System with HCS01
Страница 1: ...Rexroth IndraDrive Cs Drive Systems with HCS01 Project Planning Manual R911322210 Edition 05 ...
Страница 30: ...Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 28 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 250: ...Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 248 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 314: ...Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 312 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 318: ...Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 316 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 332: ...Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 330 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 342: ...Notes Bosch Rexroth AG DOK INDRV HCS01 PR05 EN P 340 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...
Страница 343: ...Notes DOK INDRV HCS01 PR05 EN P Bosch Rexroth AG 341 341 Rexroth IndraDrive CsDrive Systems with HCS01 ...