Operation Principles
29
www.bolid.com
−
300 ms for an intrusion alarm loop or Auxiliary alarm loop if the 300-ms Integration Time pa-
rameter is set on for this loop
For alarm loops of the Types 1, 2, 3 breaking the loop causing the device to generate an alarm can
lasts from 300 ms to 3 s depending on transient processes occurring within the loop. If high capacity
detectors are included into the alarm loop, the Alarm Integration Time increases inversely to transient
process rate. The minimum loop voltage change rate corresponding to maximum Alarm Integration
Time is 0.5 V/s.
Powering Detectors over Alarm Loops
The Signal-10 supplies power over alarm loops to two-wire fire and intrusion detectors. The number of
detectors to be included in a single alarm loop is calculated by formula:
N = Im / i , where:
N is the number of detectors in the alarm loop
Im is the maximum load current
Im = 3 m
А
for alarm loops of Types 1, 4, 6, 7, 11, 12 and Im = 1.2 m
А
for alarm loops of Type 2
i is the current in mA consumed by a detector in quiescent mode
If an alarm loop of the Type 1 (fire smoke) is in use, fire detectors must keep their operability upon lowering the
voltage until 12 V.
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......