The wiring diagram for including fire heat (normally closed) detectors into alarm loops of the Type 3 is
presented on the page 65.
Intrusion Alarm Loop (Type 4)
A loop of the Type 4 (Intrusion) is intended to involve any intrusion detectors, both normally open and
normally closed, and powered either over the loop or separately. This loop is considered to be in one of
the following statuses:
Armed
The alarm loop is monitored, its resistance being normal
Disarmed
The alarm loop is not monitored
Arming Delay
The programmed Arming Delay has not yet expired
Intrusion Alarm
The alarm loop has been broken
Arming Failed
An attempt to arm the loop has failed because the loop is broken
An Intrusion alarm loop is considered to be broken if its resistance goes out of normal range as well as
jumps by more than (provided that the 10% Deviation Blocking parameter is set off). Breaking an intru-
sion loop causes it to enter the Intrusion Alarm status.
An alarm integration time for this type of alarm loops can be 70 ms or 300 ms depending on the pro-
grammed value of the 300-ms Integration Time parameter.
Table 2 shows the matching between current resistance values and corresponding statuses of alarm
loops of the Type 4.
The wiring diagram for including intrusion detectors into alarm loops of the Type 4 is presented on the
page 65.
Intrusion Alarm Loop with Tamper Monitoring (Type 5)
A loop of the Type 5 (Intrusion with Tamper Monitoring) is intended to involve a single intrusion detector
and the tamper switch of this detector. This loop is considered to be in one of the following statuses:
Armed
The alarm loop is monitored, its resistance being normal
Disarmed
The alarm loop is not monitored
Arming Delay
The programmed Arming Delay has not yet expired
Intrusion Alarm
The alarm loop has been broken
Arming Failed
An attempt to arm the loop has failed because the loop is broken
Tamper Alarm
The enclosure of the disarmed detector has been tampered, or
short circuit failure of the disarmed loop has been detected
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......