Short-time breaking the armed loop doesn’t cause the device to consider the loop condition as an alarm
if the time of breaking doesn’t exceed:
−
50 ms if the 300-ms Integration Time parameter is off
−
250 ms if the 300-ms Integration Time parameter is on
An alarm loop of the Type 4 switches from the Armed status to the Intrusion Alarm status if:
−
The alarm loop has been broken for more than 70 ms, the 300-ms Integration Time parame-
ter being off
−
The alarm loop has been broken for more than 300 ms, the 300-ms Integration Time param-
eter being on
−
The loop resistance has jumped by more than 10%, the 10% Deviation Blocking parameter
being off for this loop
When the alarm loop has entered the Intrusion Alarm status then relay control in accordance with #1 -
#8 executive programs can be activated (if programmed).
If the parameter Auto Arming After Alarm is set on for the alarm loop then the loop will be automatically
armed and switches from the Intrusion Alarm to the Arming Delay status after its resistance being in the
normal range for a time interval more than 15 times value of the Alarm Delay configured for the loop (in
seconds).
Intrusion and Detector’s Tamper Alarms
The Signal-10 device can operate as an intrusion/detector tampering alarm control if at least one of its
alarm loops is configured with the Type 5. For such the loop the device can recognize the following sta-
tuses:
Armed
Arming Delay
Arming Failed
Disarmed
Intrusion Alarm
Short Circuit Failure
Tamper Alarm
An alarm loop of the Type 5 is considered to be in Armed status if it has been armed and its resistance
is within the normal range (see Table 2). Short-time breaking the armed loop within the time intervals
not exceeding:
−
50 ms if the 300-ms Integration Time parameter is set off
−
250 ms if the 300-ms Integration Time parameter is set on
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......