Signal-10
Operation Principles
33
www.bolid.com
№
Program
Description
Initial
Condition
6
Blink From On
Condition
The relay is switched on/off once per second if
there is an Intrusion Alarm or Fire Alarm
On
7
Blink for a Time From
Off Condition
The relay is switched on/off once per second for a
specified time if there is an Intrusion Alarm or Fire
Alarm
Off
8
Blink for a Time From
On Condition
The relay is switched on/off once per second for a
specified time if there is an Intrusion Alarm or Fire
Alarm
On
9
Lamp
In case of a Fire Alarm the relay is switched on/off
alternately twice per second
In case of a Fire Prealarm the relay is switched on
for a short time every second
In case of an Intrusion Alarm, or Entrance Alarm,
or Arming Failed the relay is switches on/off alter-
nately once per second
In case of a Trouble the relay is switched on for a
short time once per two seconds
If an alarm loop is armed the relay is switched on
If all alarm loops are disarmed the relay is
switched off
*
10
Alarm Output 1
If all the alarm loops related with the relay are
armed then the relay is switched on, otherwise the
relay is switched off
*
11
ASPT
The relay is switched on for a given time if two or
more alarm loops related with the relay have Fire
Alarm status and there are no Auxiliary loops bro-
ken. The broken Auxiliary loop will block switching
on. If the Auxiliary loop is broken while the Relay
Activation Delay has not yet expired then, after
recovering of the loop, the relay output will be
switched on for a specified time. (That is, breaking
of the Auxiliary loop temporary blocks activation
delay counting.)
Off
12
Siren
In case of a Fire Alarm the relay is switched on/off
for a specified time in mode ‘On for 1.5s and Off
for .5s’
In case of a Fire Prealarm the relay is switched
on/off for a specified time in mode ‘On for .5s and
Off for 1.5s’
In case of an Intrusion Alarm the relay is switched
on for a specified time
Otherwise the relay is off
Off
13
Fire Output
If the related loop has Fire Alarm or Fire Prealarm
status then the relay is switched on, else the relay
is switched off (open)
*
14
Trouble Output
If there are related alarm loops having Trouble,
Arming Failed, or Disarmed status, the relay is
switched off. Otherwise the relay is switched on
*
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......