Signal-10
Programming
73
www.bolid.com
The Both Power Inputs Monitoring parameter defines the conditions for the Signal-10 to switch to
the Power Failure mode: upon a power failure of a single input or both power inputs. If Both Power
Inputs Monitoring is set on, the Signal-10 switches to the Power Failure mode (see Power Failure
Mode section of this Manual) when power input voltage has dropped below 10 V at any single power
input. The device will come back to the Operation mode when the voltage has been more above 11 V
at both power inputs.
If Both Power Inputs Monitoring parameter is set off, the device keeps the Operation mode still the
power voltage exceeds 10 V at least at a single power input and switches to the Power Failure mode
if the power voltage has dropped below this value. The device returns to the Operation mode when
the power voltage of at least one power input has reached to 11 V.
To set on/off the Both Power Inputs Monitoring parameter, tick by left mouse click the simi-
larly-named box located below the toolbar at the Alarm Loops tab
The EN54 parameter defines the way for fire alarm loop (of the Types 1, 2, 3, and 14) statuses to be
displayed by the relevant device indicators. If the parameter is set off, displaying such main statuses
as Armed, Disarmed, Arming Failed and so on for fire alarm loops is similarly to that for intrusion
alarm loops.
If the EN54 parameter is set on, statuses of fire alarm loops are displayed by the following way (see
Loop Status Light and Sound section of this Manual):
−
To display Armed status the related LED is off
−
To display Disarmed status the related LED is lit yellow
−
To display Arming Failed status the related LED is flashing yellow
−
To display alarm statuses such as Fire Signal, Fire Prealarm, or Fire Alarm, the related
LED is flashing red
To set on/off the EN54 parameter, tick by left mouse click the similarly-named box located
below the toolbar at the Alarm Loops tab
The Network Address parameter is intended for unique identification of the device as a specific part
of an Orion system. The Signal-10 transmits messages from and receives network address com-
mands at the address defined by this parameter. The Network Address value must be unique for each
the device connected to an Orion network controller.
To define or change the Network Address of the device, select the Device
→
Change De-
vice Address command from the UProg main menu.
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......