Signal-10
Specifications
11
www.bolid.com
Alarm Inputs
10 inputs to monitor alarm loops
Detectors to Be Included
Addressable initiating devices DIP-34PA, IPR513-3PA,
S2000-IP-PA (up to 10 to each alarm input), or
any conventional fire and intrusion detectors intended
to be powered by a DC power supply and having the
values of internal resistance at Fire mode:
No more than 2.7 k
Ω
for normally open detectors,
At least 3.2 k
Ω
for normally closed detectors
Max Wire Resistance
(without regard to termination resistor)
1 k
Ω
for intrusion alarm loops,
100
Ω
for fire alarm loops
Min Leakage Resistance Between
Loop Wires or Between Each Wire
and the Earth
20 k
Ω
for intrusion alarm loops,
50 k
Ω
for fire alarm loops
Loop Voltage
22 V÷ 19 V if the termination resistor of 4.7 k
Ω
±5% is
brought to the loop and the value of consumed current
is 0 to 3
мА
(provided that there are no more than 3
short-circuited loops simultaneously,
27 ± 0.5 V if the alarm loop is opened
Max.Short-Circuited Loop Current
26.5 m
А
Loop Ripple Voltage
20 mV max
Solid State Relay Outputs
Commuting Voltage & Current
2 outputs ALR1 and ALR2 with normally open contacts
intended to transmit alarms and troubles to Central
Stations
350 V & 0.1
А
Transistor Outputs
Commuting Voltage & Current
Load Circuit Supervision Current
Load Circuit Protection
2 outputs with the possibilities to supervise load circuits
for open and short failures; these outputs are intended
to connect external sound and light alarms
28 V & 1
А
3 m
А
max, the alarms being off
Resettable fuses
Operating Temperatures
From
−
30
°
С
to +50
°
С
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......