![bolid Signal-10 Скачать руководство пользователя страница 89](http://html.mh-extra.com/html/bolid/signal-10/signal-10_user-manual_2785090089.webp)
Signal-10
Programming
89
www.bolid.com
Table 12. How the 1-10 Signal-10 LEDs Display a Key Status
Key Rights
to Arm/Disarm a Loop
Behavior of the Related LED
Arm/Disarm
Flashes red and green alternately
Arm Only
Flashes red
Disarm Only
Flashes green
Neither Arm Nor Disarm
Flashes yellow or is off
If needed, you can change the status of a User key inherited from the Master key initiated the key
hardware programming by long pressing on the device tamper switch. After doing so the device starts
the procedure of assigning key rights.
After tamper switch having been released the LED#1 starts blinking 2X faster, thus indicating that now
you can modify control rights of the current key for the alarm loop #1. Select appropriate rights for this
alarm loop by gradual short pressing on the tamper switch. During this process LED#1 changes its
indication in accordance with the current right settings as shown in Table 12. When a LED starts
flashing with yellow, this means that the related alarm loop is removed from the group of the alarm
loops that can be controlled with the configured key.
After selecting control rights for the current alarm loop, make long pressing on the tamper switch to
select control rights for the next alarm loop. After that the LED of the corresponding alarm loop starts
blinking 2X faster, while the LED of the previous alarm loop retains blinking (or switches OFF if no
control rights were assigned to the key for this alarm loop). Alarm loops are searched sequentially and
in closed loop manner: after programming control rights of the key for the alarm loop #10, next long
pressing the tamper switch will lead to setting control rights of the key for the alarm loop #1.
Once the status of the current key is configured, present the key to a reader in order to write the code
of the key and its modified control rights to the device non-volatile memory.
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......