Signal-10
Installation
65
www.bolid.com
Including Smoke and Heat Detectors into Alarm Loops of the Type 2
loop+
loop-
Ra
Rsh
Rt
D1
D2
D1: A smoke detector
D2: A heat detector
Ra: 0 ÷ 512
Ω
Rsh: 8.2 k
Ω
Rt:
4.7 k
Ω
Figure 5. Smoke and Heat Detectors into a Fire Loop of the Type 2 Connecting Diagram
When all the detectors are wired and connected to the relative Signal-10 inputs, test the loop. Ensure
that confirmed actuation of a single smoke detector or actuation of a heat detector causes the loop to
get the Fire Prealarm status, while actuation of two detectors (smoke or heat) causes the loop to get
the Fire Alarm status. Light and sound indication of the Signal-10 device must be in accordance with
that described in Table 8. The network controller must display the relative messages from the Signal-
10 device (see Transmitting Messages to a Network Controller section of this Manual).
Otherwise, if the test fails, the values of additional resistances have to be corrected.
Including Heat Detectors into Alarm Loops of the Type 3
LP+
LP-
4.7k
4.7k
D2
4.7k
D2
D2: A heat fire detector
Figure 6. Heat Detectors into a Fire Loop of the Type 3 Connecting Diagram
Including Intrusion Detectors into Alarm Loops of the Type 4
LP+
LP-
Rt
D1
D2
D1: A normally open intruder detector
D2: A normally closed intruder detector
Rt: 4.7 k
Ω
Figure 7. Wiring Intruder Detectors into Alarm Loops of the Type 4
Содержание Signal-10
Страница 1: ...Orion ISS Intrusion and Fire Alarm Panel Signal 10 User s Manual ...
Страница 5: ...Signal 10 General 5 www bolid com GENERAL ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...Signal 10 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 13: ...Signal 10 Operation Principles 13 www bolid com OPERATION PRINCIPLES ...
Страница 59: ...Signal 10 Installation 59 www bolid com INSTALLATION ...
Страница 61: ...Signal 10 Installation 61 www bolid com Figure 2 Signal 10 Overall and Mounting Dimensions ...
Страница 68: ...Orion ISS www bolid com 68 Figure 10 Measuring Alarm Loop Resistances by Means of UProg ...
Страница 69: ...Signal 10 Installation 69 www bolid com ...
Страница 70: ...Orion ISS www bolid com 70 PROGRAMMING ...
Страница 90: ...Orion ISS www bolid com 90 MAINTENANCE ...
Страница 95: ...Signal 10 Annex Current Consumption Estimation 95 www bolid com ...
Страница 96: ......