S2000M MAINTENANCE
GUIDE
61
Appendix
С
The list of messages being displayed
Event description
Displayed event name Category
The condition for launching of fire extinguishing equipment was met
and the launching delay is being counted
LAUNCHING DELAY
1
The pulse for fire extinguishing equipment launching was given out
LAUNCHING 1
Fire extinguishing is in process (the launching pulse was given out
and outflow of fire extinguishing agent has been detected)
EXTINGUISHING
1
The fire extinguishing equipment was not successfully launched (the
launching pulse was given out but outflow of fire extinguishing agent
has not been detected)
LAUNCH FAULT
1
The fire extinguishing equipment was launched in emergency mode
(the launching pulse was not given out but outflow of fire
extinguishing agent has been detected)
EMERGENCY LAUNCH
1
The launching of fire extinguishing equipment was blocked up (e.g.,
due to the door opening into the protected area)
LAUNCH BLOCKED
1
The launching of fire extinguishing equipment was canceled (e.g.,
due to the command "Cancel extinguish" given from console or to the
pressing "RESET" key of "S2000-ASPT")
LAUNCH CANCEL
1
Fire alarm
FIRE ALARM
1
Fire signal has been received and fire alarm is probable
FIRE PREALARM
1
Intrusion alarm
INTRUSION ALARM
2
Silent zone alarm
SILENT ALARM
2
Entry zone alarm
ENTRY ALARM
2
Open-circuit failure in the alarm loop
LOOP TRBL OPEN
3
Short circuit in the alarm loop
LOOP TRBL SHORT
3
Alarm loop has restored after any failure
LOOP TRBL RST
4
Extinguishing equipment faults
FIRE TROUBLE
3
Extinguishing equipment is in normal state
FIRE TRBL RST
3
Zone configuration parameter error
ZONE CONFIG ERR
3
Addressable detector or expander disconnection from ‘S2000-KDL’
DISCONNECTED 3
Arming has failed due to the activated status of detector
ARM FAILED
4
Zone fire alarm has been canceled. Zone is monitoring the detectors.
ALARM RESET
4
Detector status monitoring has been turned on
ARMED 5
Exit delay begins after entering arming command
ARM DELAY
5
The detector status is not monitored
DISARMED 5
Device or detector case is opened
TAMPER ALARM
3
Device or detector case is closed
TAMPER RESTORE
3
Device power supply is out of range
POWER FAILED
3
Device power supply is restored after failure
POWER RESTORE
3