FIRE AND ALARM CONSOLE
26
request the states of all connected devices loops and so on. It can take few dozen seconds
(typically) or even few minutes (maximal value). After that procedures console is ready.
Before reading and writing of ‘S2000’ console configuration by program ‘pprog.exe’, the
communication between console and program has to be set. Select ‘Devices’ tab, shoose the
console communicated COM-port number and press key ‘Start searching’. Program searchs the
connected devices, showing addresses and types of founded devices in the lower window. If the
console will be founded the reading and writing of the console configuration will be able. Main
menu of ‘S2000M’ include functions ‘Write configuration’ and ‘Read configuration’ for reading
and writing current configuration to the console memory. Read operation takes about 4 minutes,
Write operation - about 4 min 20 sec.
Attention!
During writing of the configuration it is prohibited cut off the power of the
console or exit from programming mode. If it is happened, writing operation has to be repeated.
S2000
М
COM
PC
A
B
XT1.2
3
4
PC - computer,
PI – interface converter RS-232 – RS-485
(for example, ‘PI’, ‘PI-GR’, ‘S2000-PI’),
S2000
М
- ‘S2000M’ alarm console
RS-485 A
RS-485 B
PI
RS-485
To devices
Figure 8
‘S2000M’ connection for configuration by personal computer through RS-485
interface
Configuration creating steps:
1)
Add required devices into console data base and create the partition;
2)
Define the authority levels for partition controlling, assign reguired PIN codes and
registered corresponding Touch Memory keys or Proximity cards;
3)
Set the relay output controlling;
4)
Set the event reporting to ‘S2000-K’ keyboards and ‘S2000-IT’ informators;
5)
Set the entry zones;
6)
Create user messages, if it's needed.
These steps are described in sections 2.1.7.3 - 2.1.7.7.
2.1.7.2
Adding devices into console database and partition creation
Device loops can be included in partitions, and their outputs can be automatically
controlled by ‘S2000M’ console, if these devices are presented in console database. To add the
device specify it address and type.