FIRE AND ALARM CONSOLE
52
Console supports the following operative modes through RS-232 interface:
1)
“
PRINTER
” is the mode for printering event messages;
2)
“
S2000 & PC
” – mode for operating with ‘ARM S2000’ and ’ARM ORION Pro’
programs.
3)
“
S2000 / PC
” – RS-232/RS-485 interface converter mode with auto switching in
active mode (device operation mode) when personal computer fails. It is designed to reserve
‘ARM Orion’ operations by the ‘S2000M’ console.
The default parameter value is “PRINTER”. To change parameter value make the
following steps.
Enter in programming menu (press button ‘PRG’).
Type engineer password.
Select “SETTINGS” menu item by “
4
”, “
3
” and “ENT”
keys, or press hot key “5”.
Select “RS232 SETTINGS” menu item by “
4
”,“
3
” keys and
press “ENT”, or press hot key “5”.
Indicator will displays the current operative mode. To change
mode press ‘ENT’ key.
Select new mode value by ‘
4
‘, ‘
3
‘ keys and confirm selection
by pressing ‘ENT’ key.
For working in ‘S2000 & PC’ mode set console address (see. 2.2.4.7). Fither set the
parameter “PC TIMEOUT” to the value time period reguired for computer presense analysis was
made. If computer fails after this period ‘READY’ indicator will blink (see table 1).
Give console address to work in the ‘S2000 & PC’ mode. To work in the mode “S2000 /
PC” transition delay in active mode from interface conversion mode at personal computer turn
off (parameter ‘PC TIMEOUT’ in menu ‘RS232 SETTINGS’) need to be set. Delay is given in
the seconds in range from 0 to 255 seconds. Default value of this parameter is 80 seconds.
Actions for changing this parameter are described below.
Enter in programming menu (press button ‘PRG’).
Type engineer password.
Select “SETTINGS” menu item by “
4
”, “
3
” and “ENT”
keys, or press hot key “5”.
Select “RS232 SETTINGS” menu item by “
4
”,“
3
” keys and
press “ENT”, or press hot key “5”.
Select “PC TIMEOUT” menu item. Indicator displays
parameter value. To change parameter value press “ENT”.
Input new parameter value and press key “ENT”.
2.2.4.9
The ring RS-485 interface operative mode settings
Console can work with devices through RS-485 line with ring topology. Ring topology
allows preventing the system operability loss when RS-485 line has been broken. When ring
ENTER CODE:_
RS232 MODE:
PRINTER
RS232 MODE:
v
S2000 & PC
ENTER CODE:_
PC TIMEOUT =80
PC TIMEOUT =_
v
5 SETTINGS
v
RS232 SETTINGS
v
5 SETTINGS
v
RS232 SETTINGS