S2000M MAINTENANCE
GUIDE
25
2.1.7
Console configuring
2.1.7.1
General information
If it is required to use ‘S2000-SP1’, ‘S2000-BI’, ‘S2000-K’, ‘S2000-KS’, ‘S2000-IT’
devices in the system, then console must have control rules of the devices. These rules are setup
when console is configuring.
Creating the console configuration can be done only with the help of personal computer
and program ‘
pprog.exe
’ version 2
.04
and above. The program is free. It is available on the site
www.bolid.ru
Console configuration steps are:
1) Run program ‘
pprog.exe
’. Read configuration from console or file, or create new one;
2) Correct it if necessary and save in file;
3) Write ready configuration in file.
To create new configuration by means of ‘pprog.exe’ select command ‘Create’ in menu
‘File’, or press button ‘Create new configuration’. Select console version, and press ‘OK’. The
default configuration will be created and it can be edited if necessary.
To read present configuration select command ‘Open’ in menu ‘File’, or press button
‘Open configuration file’. In window ‘Open file’ select file type, select file and press button
‘OK’. There are two available types of configuration files: text (with TXT extension) or
encrypted (with GPC extension). To read encrypted configuration file it is necessary to enter
engineer password.
To write configuration in the file select command ‘Save’ or ‘Save as’ in ‘File’ menu, or
press button ‘Save configuration file’. Configuration can be saved in text or encrypted file.
Edited configuration can be saved in a file, loaded from a file, written to the console
nonvolatile memory, or read from the console memory. To write or read the configuration
‘S2000M’ console has to be connected to personal computer. The console can be connected both
via RS-232 or RS-485 interfaces. In the first case console is connected to computer as shown on
the Figure 5, and the second case is shown on the Figure 8.
Set console programming mode:
press ‘PRG’ key;
enter engineer password (default value - <123456>) and press
‘ENT’ key;
select menu item ‘SETTINGS’ by keys ‘
t
‘ and ‘
u
‘ and
‘ENT’, or press key ‘5’;
select menu item ‘REMOTE PROGRAM’ by keys ‘
t
‘ and ‘
u
‘
and ‘ENT’, or press key ‘6’;
the LCD will display ‘PROGRAMMING MODE’ indicating the
console status.
Console in programming mode allow to write and to read the configuration by means of
program ‘
pprog.exe
’. When in programming mode the console should have a unique address in
‘RS-485’ interface address range. Its default value equal 127 and can be changed (see. item 0).
Refer to the ‘
pprog.exe
’ user’s manual for procedures for console configuring. To exit from
programming mode press console key ‘CLR’. The console will return to operating mode and
ENTER CODE:
v
REMOTE PROGRAM
PROGRAMMING MODE
v
5 SETTINGS