7. BOILER OPERATION AND CONTROL WHEN OPERATED WITH
OTHER SUITABLE FUEL
7.1. BOILER FUEL LOADING AND IGNITION
Hot water boilers series Bisolid Automat are designed to work with preferred
fuel (wood pellets) and can utilize other suitable fuel (firewood and wood chips).
The working algorithm requires the presence of pellets because the ignition of
the other suitable fuel and optimal burning is assisted by the pellet burner
operation. In principle, it is possible work only with pellets, but the optimal use
of the opportunities of boilers, and heat output becomes both fuels
.
It is forbidden directly ignition of hot water boilers series Bisolid Automat using
other suitable fuel (fire wood or wood chips) without to be switch on the pellet
burner controller!
Switch on the pellet burner controller before starting operation of the
boiler!
The user firstly has to start boiler operation in preferred fuel mode (wood
pellets) With purpose to be heated flue gases system (minimum 30 min. in
nominal heating output) and after that the boiler to go in the operation mode
with other suitable fuel (firewood or wood chips).
Before igniting other suitable fuel in the form of firewood and wood chips in Bisolid Automat
series hot water boilers check:
Water quantity in the heating system.
Sealing of the heat-exchanger cover.
Installed pellet tube burner condition.
The flue gases flap should not be left opened except for 1-2 minutes while
loading the boiler fuel hopper with other suitable fuel (firewood and wood chips).
The role of the flue gases flap is to bring the flue gases out of the boiler fuel hopper to the
chimney only during loading other suitable fuel. The flue gases flap is opened before opening
the door for loading the boiler other suitable fuel to enable extraction through the chimney of
the flue gases collected in the combustion chamber. This prevents smoke in the boiler room
and the risk of inhaling flue gases while loading other suitable fuel in the boiler. The flue gases
flap should no be opened for more than one or two minutes i.e. only during loading the hopper
with other suitable fuel, and should be closed immediately after that.
Do not start the boiler, before connecting the boiler to the chimney.
Check chimney connections before starting the boiler.
Check chimney draft. If the draft exceeds the recommended values install a
draft regulator.
In the transition seasons it is recommended boiler operation
ONLY
with wood
pellets, in order to avoid the danger of overheating when is used fuel in the
type of firewood or wood chips.
Other suitable fuel ignition (firewood and wood chips) is done as follows: