INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bisolid Automat OM-BAV05/02/2018/EN
71
10. TROUBLESHOOTING
10.1. BOILER TROUBLESHOOTING
Failure
Reason
Solution
The boiler can not reach
its rated power
Unsealed soot door
Fasten all ash door nuts, if necessary
replace door sealing
Unsealed heat-exchanger cover
and fuel feeding door
Check sealing ropes, correct sealing
ropes positioning, if necessary replace
sealing ropes.
Insufficient chimney draft.
Perform chimney draft checks and take
corrective measures.
Used fuel is with low calorific value. Use the prescribed fuel type with
appropriate calorific value, especially in
low outside temperatures.
Caused by improper pellet burner
operation
Refer to the section on description,
commissioning and operation of tube
pellet burner series Bisolid GP xx_B
thc.
Boiler power can not be
regulated
Unsealed fuel feeding and ash
cleaning doors
Check sealing ropes, correct sealing
ropes positioning, if necessary replace
sealing ropes.
Too high chimney draft
Half-close the valve in the chimney
pipe, if necessary perform chimney
draft checks and take corrective
measures.
High water temperature in
the boiler and low water
temperature in the
radiators. Water in the
boiler boils.
High hydraulic resistance of the
heating system, especially in the
standalone system.
Perform system cleaning with rinse, if
necessary install circulation pump.
Too high chimney draft
Reduce chimney draft by using a
chimney damper.