Excess heating of the
pellet feeding pipe.
Insufficient chimney draft or
contaminated equipment.
Clean the equipment and the chimney,
if necessary. Possible solution is to
install additional flue gas fan and/or
change the chimney.
Heating the pellet
feeding pipe and
emergency thermostat
activation
Low chimney draft or
contaminated with ash particles
equipment.
Clean the equipment and the chimney
if necessary. Restart the burner
Possible solution is to install additional
flue gas fan and/or change the
chimney line.
Polluted and/or melted
photo-sensor.
Improper shut down of the burner
Clean the photo-sensor surface or
replace it withnew one. Observe the
burner shut down procedure,
presented in the manual.
Presence of unburned
fuel over the combustion
chamber grate.
Inefficient fuel combustion.
Adjust operation parameters of the
equipment - adjustment is needed
and/or consultation with an authorized
technician.
Slag deposits on the
combustion chamber
grate.
Fuel used is with high ash content
and does not comply with the
equipment requirements.
Change the fuel with a new one
complying with the requirements for
reliable operation of the burner.
Burner operation mode exceeding
the rated thermal power.
Reduce the burner thermal power by
changing its thermal power rate.
Error message,
displayed on the
controller display
Problem in the burner operation.
It is possible to seek consultation /
intervention by a service technician
The burner has stopped,
but after new start it
operates.
The photo-sensor sends wrong
information to the controller.
Check the amount of the fuel on the
grate. Seek assistance by a service
technician for consultation or
adjustment.
High temperature of the
flue gases (if a
thermometer is installed)
Dirty heat-exchanging surfaces
depending on the equipment type
and operation mode.
Clean the heat-exchanging surfaces of
theequipment.
Smoke in the boiler
room after a certain
period of operation
Dirty or clogged with ash flue line
for extracting the flue gases from
the heat consuming equipment.
Clean the heat consuming equipment
from the ash deposits.
Failure of the burner
cleaning device.
The cleaning cannot be done
properly
Competent consultation and / or
intervention by a service technician is
needed.
Other failures not
described above
Competent consultation and / or
intervention by a service technician is
needed.
In all other cases, the repair of any failure and damage should be performed by the
manufacturer or an authorized service provider.
An obligatory condition for the normal operation is the presence of pellets, as
main fuel. Loading wood chips, as other suitable fuel
to be made in operating
burner
at steady state (presence of stable flame). Loading of firewood can be
made as in already operated burner, and in the absence of equipment start.
The requirement for the second case is loading with wood to be realized in the
way to is not to close burner tubus, i.e. to provide normal flame output. There is
possibility to realized start delay of the equipment – the preliminary loaded
boiler with wood is automatically ignites by external start (for example GSM) or
with
или
by simply pressing of the switch START. This is significant advantage
if this facility – automatic ignition of the other suitable fuel (even wood with high
moisture, difficult to burn in, hard flammable at normal boiler). The other
suitable fuel loading is made in open flue gases flap to the chimney with
purpose to limit smoke forming at the cover opening for loading.
Содержание Automat 25
Страница 2: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL Bisolid Automat OM BAV05 02 2018 EN 2...
Страница 70: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL Bisolid Automat OM BAV05 02 2018 EN 70...
Страница 75: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL Bisolid Automat OM BAV05 02 2018 EN 75...