INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bisolid Automat OM-BAV05/02/2018/EN
67
Figure 26. Recommended chimney system dimensions
The dimensions of the smoke extractor and the chimney must not be smaller than the chimney
neck dimension from the boiler. The diagram in Figure 27 is recommended for dimensioning of
the total height and minimum inner diameter of the chimney, depending on the boiler heat
output if it is not explicitly stated in the mandatory local regulations.
If the chimney draft is insufficient or chimney is not built according to the project
(bad condition of the structure, without insulation, blocked etc.) can occur big
problems in combustion. In this case, we strictly recommend the chimeny
condition to be controlled by the technician who will identify and remedy any
irregularities.
A hole with
lid for
inspection
Draft limiter
Smoke extractor
Chimney