MK (E3) 07/2009
page 32/70
Behavior after completing the program:
The controller changes to Idle Mode. The heating is inactive; the chamber approximates ambient tem-
perature. The fan is operating. The toggling states of the operation lines are OFF.
9.2
Selecting between set-point ramp and set-point step
Temperature set-points always refer to the start of a program section, i.e., at the beginning of each pro-
gram section the entered temperature set-point is targeted. During program section operation, the tem-
perature gradually passes to the set-point entered for the following program section.
By appropriate design of the program section timing, you can program all kinds of temperature transi-
tions.
•
Gradual temperature changes “set-point ramp”
The temperature set-point gradually moves from one set-point to the one of the following program sec-
tion during a given interval. The actual temperature value (X) follows the continually moving set-point
(W) at any moment.
•
Program sections with constant temperature
The initial values of two subsequent program sections are identical; so the temperature remains con-
stant during the whole time of the first program section.
•
Sudden temperature changes “set-point step”
Steps are temperature changes (ramps) that occur during a very short interval. A section with a differ-
ent set-point follows two program sections with an identical set-point. If the duration of this transitional
program section is very short (minimum entry 1 sec), the temperature change will proceed rapidly in
the possible minimum time.
01
02
03
04
05
06
07
08
09
W
t
Figure 8: Possible temperature transitions
The following chapter offers examples of programming a set-point ramp and a set-point step.
9.3
Program entry as set-point ramp or as set-point step
In order to avoid incorrect programming, we recommend plotting the temperature profile (chart template
in chap. 9.9) and entering the values into a table (templates in chap. 9.10).
The controller provides 8 operation lines that can be activated or de-activated for each program section.
Operating contact 1 is used to control the bedew protection (chap. 10). Operation lines 2 to 5 can be
used to switch any device connected to the zero-voltage relay outputs (DIN sockets (8) and (9), chap.
14.6). The other operation lines are non-functional.
Содержание 9020-0146
Страница 65: ...MK E3 07 2009 page 65 70 18 9 Dimensions MK 115 ...
Страница 71: ......