5.2.2.1
Analog Module in IP20, 2 Channels and in IP65
AS-Interface parameter bit 0: Filter for mains frequency:
The 50 Hz filter is valid in the whole of Europe.
AS-Interface parameter bit 1: Configuration of channel 2
By means of AS-Interface parameter bit 1 it is possible to adjust whether measu-
ring channel 2 of the analog input module is active or not. Deactivating channel 2
shortens the conversion and transmission time and influences LED and peripheral
fault messages. LED displays and peripheral fault messages are not affected by
this channel anymore.
By deactivating channel 2 conversion and transmission time in the AS-Interface
slave can be intensely reduced (for additional information see chapter 5.2.4 re-
spectively chapter 5.3.4).
Additionally it is possible by the analog input module in IP20, that the 2. channel
ist switched off with a switch inside the device.
Therefore the case of the module has to be opened as follows and the switch to
be adjusted:
1. Unlocking of the module´s top
2. Openning the module
Pull out the top until stop
3. Adjusting the supply.
P0 filter in the A/D converter for
1
50 Hz (default)
0
60 Hz
P1
channel 2
1
configured (active)
0
not configured (not active)
On both sides of the module force the unlock buttons with help of
a screw driver
ON: Channal 2 on
OFF: Channal 2 off
ON
OFF