![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672009.webp)
AS-Interface Analog Module
General Information
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
9
3.1
Technical Overview of all Modules
3.1.1
Analog Modules with 2 Channels in Protection Category IP65
LED displays:
LED (green) Analog 1: State of channel 1
LED (green) Analog 2: State of channel 2
LED (green) Analog 3: State of channel 3 (only for Pt100 module)
LED (green) Analog 4: State of channel 4 (only for Pt100 module)
LED (green) power:
Voltage 24 V out of AS-Interface for analog
part OK (not for Pt100-Module)
LED (green) AS-i:
Voltage on AS-Interface terminals OK
LED (red) FAULT:
AS-Interface communication fault, peripheral fault
3.1.2
Analog Modules with 2 Channels in Protection Category IP20
Features
Current input
Voltage input
Current output
Voltage output
Pt100
Number of inputs
2
2
4
Number of out-
puts
2
2
Resolution
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
Kind of measu-
ring
curren
voltage
temperature
Kind of output
current
voltage
Display of chan-
nel states
yes
yes
yes
yes
yes
Potential relati-
onship between
sensors/aktua-
tors/Pt100 and
AS-Interface
• +24 V out of AS-Inter-
face:
potential connected to
AS-Interface
• +24 V out of external
help voltage:
galv. seperation
• +24 V out of AS-Inter-
face:
potential connected to
AS-Interface
• +24 V out of external
help voltage:
galv. seperation
• +24 V out of AS-Inter-
face:
potential connected to
AS-Interface
• +24 V out of external
help voltage:
galv. seperation
• +24 V out of AS-Inter-
face:
potential connected to
AS-Interface
• +24 V out of external
help voltage:
galv. seperation
potential connec-
ted to AS-Interface
AS-Interface
parameters
P0: 1 50 Hz filter
0: 60 Hz filter
P1: 1: channel 2 on
0: channel 2 off
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1 50 Hz filter
0: 60 Hz filter
P1: 1: channel 2 on
0: channel 2 off
P2: 1: P-error allowed
0: not allowed
P3: not used
P0, P1, P3:
not used
P2: 1: P-error allowed
0: not used
P0, P1, P3:
not used
P2: 1: P-error allowed
0: not used
P0: 1: 50 Hz filter
0: 60 Hz filter
P1, P2:
P-error release
of cannel
P3: sensor
1: 2-wire
0: 3-wire
Features
Input
Output
Number of inputs
2
2
Number of outputs
Resolution
16 Bit A/D
16 Bit
Kind of measuring
channelwise
• voltage
• current
Kind of output
channelwise
• voltage
• current
Display of channel states
yes
yes
Potential relationship between
analog part and AS-Interface
power supply of the sensors can be made of either
out of AS-Interface or out of external help voltage by
slide switch S1:
• +24 V out of AS-Interface:
potential connected to AS-Interface
• +24 V out of external help voltage:
galv. speration
power supply of the sensors can be made of either
out of AS-Interface or out of external help voltage by
slide switch S1:
• +24 V out of AS-Interface:
potential connected to AS-Interface
• +24 V out of external help voltage:
galv. sperationnnung:
AS-Interface parameters
P0: 1 50 Hz filter
0: 60 Hz filter
P1: 1: channel 2 on
0: channel 2 off
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1 automatic recognition
0: mode changeable through P1, P3
P1: 1: channel 1 current
0: channel 1 voltage
P2: 1: P-error allowed
0: not allowed
P3: 1: channel 2 current
0: channel 2 voltage
Feature
Cannel 2 can be switched off with switch S2