AS-Interface Analog Module
General Information
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
11
3.1.4
Analog Modules with 4 Channels, M12 Connection in Protection
Category IP65
LED displays:
LED (yellow) In 1/Out 1: State of channel 1
LED (yellow) In 2/Out 2: State of channel 2
LED (yellow) In 3/Out 3: State of channel 3
LED (yellow) In 4/Out 4: State of channel 4
LED (green) AUX:
External help voltage 24 V OK (not for Pt100 module)
LED (green) PWR:
Voltage on AS-Interface terminals OK
LED (red) FAULT:
AS-Interface communication fault, peripheral fault
3.2
Analog Modules with 2 Channels in Protection Category IP65
The range consists of 5 AS-Interface analog modules:
2 analog inputs 0 - 10 V, 2 analog inputs 4 - 20 mA, 4 analog inputs Pt100, 2 ana-
log outputs 0 - 10 V, 2 analog outputs 0 - 20 mA.
3.2.1
Analog Modules with 2 Inputs
The analog modules have 2 analog inputs. The conversion of the measured value
and the data transmission via AS-Interface occurs asynchronically according to
AS-Interface Profile 7.3. 2 analog sensors can be connected via cage clamp ter-
minals. The sensors can be supplied by AS-Interface or external help voltage (ac-
cording to PELV) via the black ribbon cable. The resolution of the analog data is
16 Bit. The analog modules contain 50 Hz and 60 Hz filters. These filters can be
optionally switched with the help of the AS-Interface parameters.
The measuring range of voltage input modules amounts to 0 - 10 V and of current
input modules 4 - 20 mA.
3.2.2
Analog Modules with 2 Outputs
The analog modules have 2 analog outputs. The digital-analog conversion and the
data transmission via AS-Interface occurs asynchronically according to AS-Inter-
face Profile 7.3. 2 analog actuators can be connected via cage clamp terminals.
Features
Current intput
Voltage input
Current output
Voltage output
Pt100
Number of inputs
4
4
4
Number of out-
puts
4
4
Resolution
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
Kind of measu-
ring
current
voltage
temperature
Kind of output
current
voltage
Display of chan-
nel states
yes
yes
yes
yesja
yes
Potential relati-
onship between
sensors/aktua-
tors/Pt100 and
AS-Interface
galvanical speration
galvanical speration
galvanical speration
galvanical speration
galv. speration
AS-Interface
parameters
P0: 1 bridge active
0: bridge not active
P1, P2: channel on/off
P3: 1: P-error allowed
0: not allowed
P0: not used
P1, P2: channel on/off
P3: 1: P-error allowed
0: not allowed
P0: 1 Profile 7.3 is
monitored
0: Profile 7.3 is not
monitored
P1: not used
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1 Profile 7.3 is
monitored
0: Profile 7.3 is not
monitored
P1: not used
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1: 50 Hz filter
0: 60 Hz filter
P1, P2:
P-error release
of cannel
P3: sensor
1: 2-wire
0: 4-wire