![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672062.webp)
AS-Interface Analog Module
Operating the Modules
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
62
5.2.4.2
Transmission Time of Analog Parameters for 3 Channels
The conversion time of 3 analog input signals into digital signals amounts to
180 ms.
The transmission time of 3 16 bit parameters via the AS-Interface amounts - in
worst case - to 7 AS-Interface cycles per parameter. With one cycle period being
5 ms per AS-Interface cycle this sums up to a transmission time of 3 * 7 *
5 ms = 105 ms via AS-Interface.
The transmission time for transmission of 3 analog parameters totals - in worst
case - to 180 ms + 105 ms = 285 ms..
5.2.4.3
Transmission Time of Analog Parameters for 4 Channels
The conversion time of 4 analog input signals into digital signals amounts to
240 ms.
The transmission time of 4 16 bit parameters via the AS-Interface amounts - in
worst case - to 7 AS-Interface cycles per parameter. With one cycle period being
5 ms per AS-Interface cycle this sums up to a transmission time of 4 * 7 *
5 ms = 140 ms via AS-Interface.
The transmission time for transmission of 4 analog parameters totals - in worst
case - to 240 ms + 140 ms = 380 ms..