AS-Interface Analog Module
Operating the Modules
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
60
AS-Interface parameter bits 1 and 2: Switching on/off of channels 2 - 4
With the help of these parameter bits the channels 2 - 4 can be switched on or off
each.
AS-Interface parameter bit 3: Display of a peripheral fault
By means of this bit, it is possible to adjust whether an adjacent peripheral fault is
notified by the flashing "FAULT"-LED of the module and the peripheral fault is
transmitted to the AS-Interface master.
5.2.3
Measuring Range of Analog Input Modules
Analog input module 2/4 inputs, 4 - 20 mA:
The channel 1 is switched on ever und can not be switched off.
analog input is
P1 P2
1
2
3
4
0
0
on
off
off
off
0
1
on
on
off
off
1
0
on
on
on
off
1
1
on
on
on
on
P3 peripheral fault is
1
notified
0
not notified
Range 4 … 20 mA Units dec. Units hex. Analog LED Region
>23 mA
32767
7FFF
flashing
Overflow
23 mA
23000
59D8
…
…
…
on
Overrange
20,001 mA
20001
4E21
20 mA
20000
4E20
19,999 mA
19999
4E1F
…
…
…
on
Nominal range
4,001 mA
4001
0FA1
4 mA
4000
0FA0
3,999 mA
3999
0F9F
…
…
…
on
Underrange
1 mA
1000
03E8
<1 mA
32767
7FFF
off
Wire break