![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672036.webp)
AS-Interface Analog Module
Connections, Displays and Operating Keys
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
36
4.5.1.2
Pin Configuration of the Analog Output Module (0 … 20 mA) in IP65 with
2 Channels
Connection of an actuator without separate power supply to the analog out-
put module (0 … 20 mA) in IP65 with 2 channels:
A 2-wire-actuator is attached to terminal 8 (Sig.+) and 10 (Sig.-) of channel 1.
Corresponding channel 2 is attached via 2 (Sig.+) and 4 (Sig.-).
Connection of an actuator with own power supply to the analog output mod-
ule (0 … 20 mA) in IP65 with 2 channels:
An actuator with own power supply (e. g. an ampmeter) is attached to terminal 8
(Sig.+) and 10 (Sig.-) of channel 1.
Corresponding channel 2 is attached via 2 (Sig.+) and 4 (Sig.-).
Analog module
Actuator without separate 24 V supply
Analog module
Actuator with own power supply
24V ext.
Sig.+
Sig.-
0V ext.
24V ext.
Sig.+
Sig.-
0V ext.
supply PELV
without earth
connection