![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672010.webp)
AS-Interface Analog Module
General Information
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
10
LED displays:
LED (green) Input 1/Output 1: State of channel1
LED (green) Input 2/Output 2: State of channel 2
LED (green) Input 1/Output 1: Voltage/current channel 1
LED (green) Input 2/Output 2: Voltage/current channel 2
LED (green) PWR:
Voltage on AS-Interface terminals OK
LED (red) FAULT:
AS-Interface communication fault, peripheral
fault
LED (green) AUX:
External help voltage 24 V OK
LED (green) INT:
Voltage supply out of AS-Interface for analog
part OK
3.1.3
Analog Modules with 4 Channels in Protection Category IP20
LED-Anzeigen:
LED (yellow) I1/O1: State of channel 1
LED (yellow) I2/O2: State of channel 2
LED (yellow) I3/O3: State of channel 3
LED (yellow) I4/O4: State of channel 4
LED (green) DIAG: Diagnosis
LED (green) AUX:
External help voltage 24 V OK (not for Pt100 module)
LED (green) PWR: Voltage on AS-Interface terminals OK
LED (red) FAULT:
AS-Interface communication fault, peripheral fault
Features
Current intput
Voltage input
Current output
Voltage output
Pt100
Number of inputs
4
4
4
Number of out-
puts
4
4
Resolution
16 Bit
16 Bit
16 Bit
16 Bit
16 Bit
Kind of measu-
ring
current
voltage
temperature
Kind of output
current
voltage
Display of chan-
nel states
yes
yes
yes
yes
yes
Potential relati-
onship between
analog part and
AS-Interface
galvanical speration
galvanical speration
galvanical speration
galvanical speration
galv. speration
AS-Interface
parameters
P0: 1 50 Hz filter
0: 60 Hz filter
P1, P2: channal on/off
P3: 1: P-error allowed
0: not allowed
P0: 1 50 Hz filter
0: 60 Hz filter
P1, P2: channal on/off
P3: 1: P-error allowed
0: not allowed
P0: 1 Profile 7.3 is
monitored
0: Profile 7.3 is not
monitored
P1: not used
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1 Profile 7.3 is
monitored
0: Profile 7.3 is not
monitored
P1: not used
P2: 1: P-error allowed
0: not allowed
P3: not used
P0: 1: 50 Hz filter
0: 60 Hz filter
P1, P2:
P-error release
of cannel
P3: sensor
1: 2-wire
0: 4-wire