![bihl+Wiedemann AS-Interface 2.1 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/bihl-wiedemann/as-interface-2-1/as-interface-2-1_user-manual_2750672061.webp)
AS-Interface Analog Module
Operating the Modules
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
61
When switching channel 2 from active to inactive condition its last value is shown.
Input resistor:
50 Ohm
Max. input current:
40 mA
Wire break detection: yes
Analog input module 2/4 inputs, 0 - 10 V:
When switching a channel from active condition to inactive condition its last value
is shown.
Max. voltage:
50 V
Input resistance:
100 kOhm
Wire break detection: yes
5.2.4
Transmission Time of Analog Parameters
The transmission time of analog parameters depends on the one hand on the con-
version time of analog signals to digital signals in the AS-Interface module, on the
other hand on the transmission time via the AS-Interface.
5.2.4.1
Transmission Time of Analog Parameters for 2 Channels
The conversion time of 2 analog input signals into digital signals amounts to
120 ms. When channel 2 is inactive, the conversion time of one channel is reduced
to only 20 ms.
The transmission time of 2 16 bit parameters via the AS-Interface amounts - in
worst case - to 7 AS-Interface cycles per parameter. With one cycle period being
5 ms per AS-Interface cycle this sums up to a transmission time of 2 * 7 *
5 ms = 70 ms via AS-Interface.
When channel 2 is inactive, the transmission time via AS-Interface for just one
channel amounts to 7 AS-Interface cycles. With one cycle period being 5 ms per
AS-Interface cycle this sums up to a transmission time of 1 * 7 * 5 ms = 35 ms via
AS-Interface.
The transmission time for transmission of 2 analog parameters totals - in worst
case - to 120 ms + 70 ms = 190 ms. When channel 2 is disconnected it can be re-
duced to a minimal total of 20 ms + 35 ms = 55 ms.
Range 0 … 10 V
Units dec. Units hex. Analog LED Region
> 11,5 V
32767
7FFF
flashing
Overflow
11,5 V
11500
2CEC
…
…
…
on
Overrange
10,001 V
10001
2711
10 V
10000
2710
9,999 V
9999
270F
…
…
…
on
Nominal range
1 mV
0001
0001
0V
0000
0000
< 0V
0000
0000
on
Underflow