LB 470 Level
7 Main Menu Device Setup
56925BA2 Rev. 03, 11/2017
99
Detector settings: Detector Service | Reset Detector
Device settings | Setup | Sensors | [NAME DETECTOR] | Detector Service | Reset De-
tector
In the submenu
″
Reset Detector
″
, the detector can be restarted and be reset to the
factory settings.
1
2
3
4
Button Restart
Button Factory settings
Window "Warning: Reboot"
Window "Warning: Factory Reset"
Fig. 78
Reset Detector
IMPORTANT
The measurement is interrupted during a restart.
1.
To restart the Detector, click the button
<Reboot>
(Fig. 78, item 1).
A window with a warning "Reboot" (Fig. 78, item 3) opens.
2.
Click on
<Yes>
to confirm.
The device is restarted.
IMPORTANT
All custom configuration settings will be lost with a reset to factory settings!
1.
To reset the detector to the factory settings, click the button
<Factory reset>
(Fig. 78, item 2).
A window with the warning Factory settings (Fig. 78, item 4) opens.
2.
Click on
<Yes>
to confirm.
The device is reset to factory settings and restarts.
Содержание Duo Xpert
Страница 2: ......
Страница 4: ......
Страница 119: ...LB 470 Level 7 Main Menu Device Setup 56925BA2 Rev 03 11 2017 119...
Страница 181: ...LB 470 Level 12 Appendix 56925BA2 Rev 03 11 2017 181...
Страница 183: ...Unit d valuation D tecteurs LB 47x LB 4700 Informations sur la s curit 56925BA59 Rev No 01 11 2017...
Страница 184: ......
Страница 190: ...1 A propos de ce manuel d utilisation LB 470 Niveau Level 8 56925BA59 Rev 01 11 2017...
Страница 196: ...Level F llstand Technical Information Technische Information 56925TI1L Rev No 00 11 2017...
Страница 208: ...Technical Information Level Technische Information F llstand 56925TI1L Rev 00 11 2017 Evaluation unit Auswerteeinheit...
Страница 227: ...Technical Information Level Technische Information F llstand 56925TI1L Rev 00 11 2017...