Ø
Negative Alarm Line
devices activated by negative
positive on the relevant terminal.
Ø
Balance Alarm Line
devices activated by imped-
ance unbalance on the relevant terminal.
This Control panel has 6 Outputs — expandable to 118
by means M-OUT/6 Outputs Expanders:
6 Outputs
on the Main Unit
96 Outputs
16 Outputs
118Outputs
on 16 Output Expanders (6 Outputs per
Expander)
On 16 LED Keypads (1 Output per Key-
pad)
(116 for KYO 100) Total
The three Outputs on the Main Unit (no. 1, 2, and 3)
comprise terminals:
Ø
+N1, +A1, C1-NC1-NA1
Ø
+N2, +A2, C2-NC2-NA2
Ø
+N3, +A3, C3-NC3-NA3 (KYO 300 only)
All other Outputs comprise terminals OC1, OC2, etc.
The Standby status of the Outputs can be programmed
as follows:
Ø
[+N] terminals can be connected to positive (13.8 V)
or can be open, and therefore can be used to activate
Intrinsic Security
Devices;
Ø
[+A] terminals can be open or connected to positive
(13.8 V), and therefore can be used to activate
Posi-
tive Alarm Line
devices;
Ø
[C] terminals can be connected to their respective
terminals [NC] or [NA], and therefore, can be used to
activate all types of signalling devices;
Ø
[OC] terminals can be open or connected to nega-
tive, and therefore, can be used to activate
Negative
Alarm Line
devices
+
The OC terminals on the Main Unit can switch a
maximum of 1 A whereas, the OC terminals on the
Output Expanders can switch a maximum of
0.15 A. An
Omnia/4R
Relay board is required to
switch higher values.
The activation/restoral of Outputs depends on various
parameters (refer to “Outputs” under “PROGRAMMING
FROM PC”).
The wiring diagram in Fig. 20 illustrates connection of a
Self-powered Siren and an Indoor Siren to Outputs
no. 1 and no. 2 on the Main Unit:
Ø
Outputs no. 1 and no. 2 on the Main Unit are pro-
grammed as Normally Closed;
Ø
[+N]
is the positive power and Input of the Self-pow-
ered Siren. The Siren will activate when positive
(13.8 V) fails on the [+N] terminal;
Ø
[+B]
is the positive power and Input of the Indoor Si-
ren. The Siren will activate when positive (13.8 V) is
applied to the [+N] terminal;
Ø
[
M
] and
[GND]
are the negative power terminals of
the Self-powered Siren and Indoor Siren;
Ø
[A.S.]
and
[AS1-AS2]
are the Normally Closed Tam-
per contacts of the Self-powered Siren and Indoor Si-
ren.
To provide Tamper detection: connect the Signalling
device Tamper contact to the Control panel Tamper
Line or to a 24h zone (refer to “Connecting Tamper
Contacts”).
KYO 300-KYO100
INSTALLING
25
+A2+N2
self-powere
siren
Panel
A. S.
AS1 AS2
GND
+B
+A1+N1
indoor
siren
tamper line
+N
Figure 20
Connecting a Self-powered Siren and an Indoor Siren to Main Unit Outputs no. 1 and no. 2