
negative;
– the zone will trigger Tamper when open;
– the zone will trigger Alarm under all other conditions.
+
Zones with Double balance can detect and signal
Alarm and Tamper by means of just two wires.
To provide Tamper detection on zones with Normally
Closed or 10 K balance:
either
connect the detector tamper contact to the Con-
trol panel Tamper Line — this type of connection does
not provide identification of the tampered detector;
or
connect the detector tamper contact to a 24h zone —
this type of connection requires two zones — one for
Alarm detection, and the other for Tamper detection (re-
fer to “Connecting Tamper Contacts”).
n
Glass Break Detectors
Fig. 18 illustrates the connection of 3 Glass Break de-
tectors to a zone with Glass Break balance.
!
Glass Break zones accept up to 20 detectors.
The continuous lines in the wiring diagram represent
the soft-soldered conductors of the detector, and the
broken lines represent the copper wires.
Connect the Glass Break detectors in parallel between
the zone and negative, and a 10 k
W
resistor in parallel
to the last detector.
This balance type will allow the Control panel to detect
Alarm, Tamper and Short-circuit on the zone:
– the zone will hold Standby status whilst connected to
negative via a 10 K
W
resistor;
– the zone will trigger short-circuit when connected to
negative;
– the zone will trigger Tamper when open;
– the zone will trigger Alarm under all other conditions.
n
Connecting Fire Detectors
The KYO300 accepts Fire detectors with Alarm -Repeat
Outputs that operate at 12 V (e.g. BENTEL SECURITY
RT101, RT102 and RF501t).
See Fig. 19 for the wiring diagram.
Connect the Alarm-Repeat Outputs of the Fire detec-
tors in parallel to a
FIRE
zone (
Normally Open — 24h
).
Connect the positive supply terminal of the detectors to
terminals
[+F]
.
Connect the negative supply terminal of the Fire detec-
tors to an Open-Collector Output programmed as:
–
Monostable
– Normally Closed
– 20 seconds ON Time
Assign the Output to an event that will reset the Fire de-
tectors (e.g. Reset Panel or Reset Partition).
In this way, when the programmed event occurs, the
negative power supply to the fire detectors will be inter-
rupted for 20 seconds thus resetting the Fire detectors.
Connecting Alarm Signalling Devices
Alarm Signalling Devices, such as: Self-Powered Si-
rens, Indoor Sirens, Telephones Diallers, etc., can be
classified as follows:
Ø
Intrinsic Security Devices
(e.g. Self-Powered Si-
rens) activated by voltage failure on the relevant ter-
minal;
Ø
Positive Alarm Line
devices(e.g. Indoor Sirens) ac-
tivated by positive (12 V) on the relevant terminal.
24
fire
detector
fire
detector
fire
detector
+A
+A
+A
R
R
R
+B
+F
OC1
L2
+B
+B
–
–
–
+F L3
+F L4
Panel
Input exp.
Panel
Output exp.
Keypad
Figure 19
Connecting 3 Fire Detectors to a Zone with Normally Open balance