Temporary disarming (patrol)
This application allows one or more partitions to be disarmed temporarily for patrol purposes. In this way, security
staff will be able to enter the temporarily disarmed area without generating alarms.
If the following Academy40 items are used:
Ø
Event no. 417:
Recognized user code 10 [Code 010]
Ø
Output no. 4:
corresponds to terminal [OC2] of the Main unit
Ø
Zones no. 6 and 7:
correspond to terminals [L6] and [L7] of the Main unit. Connect as per figure 43 and refer to
the following programming instructions.
Codes
Program
Pr. 10 Code
as follows:
Ø
Description:
Patrol
Ø
Available
Ø
Active
Ø
Enables user menu:
none
Ø
Enable instant actions
:
none
Codes programmed in this way will be enabled for the patrol use only.
Event-Actions
Program
event no. 417
---- Recognized user code 10 [Code 010] as follows:
Ø
Output ON
: 4
Outputs
Program
Output no. 4
as follows:
Ø
Type:
Monostable
Ø
Attribute:
Normally open
Ø
Time:
On time [patrol time + 1]
Min
.
Zones
Program
Zones no. 6 and 7
as follows:
Zone no. 6
Zone no. 7
Command
Command
Ø
Command:
Disarm only
Arm only
Ø
Balancing:
Normally open
Normally open
Ø
Sensitivity:
Standard - 1 pulse
Low - Pulse length
[Patrol time]
Min.
Ø
Cycles:
Repetitive
Repetitive
Ø
Partition:
Select the partitions that will be disarmed for the patrol time----for both zones.
Enter code no.10 then press the Enter key to disarm the programmed partitions for the programmed time. The par-
titions will re-arm automatically.
To refresh the patrol time:
----allow the programmed time to elapse;
----wait 60 seconds then enter the patrol code.
+
If the patrol code is entered when the patrol time is running it will be ignored.
L7
L6
Main unit
Output no. 4:
Monostabe
Normally open
On Time -
- [patrol time + 1] Min.
Zone no. 7:
Command
Only arm
Normally open
Sensitivity - Low
Pulse length -
- [patrol time] Min.
Zone no. 6:
Command
Only disarm
Normally open
Sensitivity - Standard
Pulses - 1
Figure 43
Temporary disarming (patrol)
70
Expandable Multifunction Control Panel