Stop Alarm by Digital key
Outputs (e.g. Sirens) and calls activated by false alarms can be stopped.
The quickest way to stop a false alarm is to use a valid digital key----enabled on the partition in Alarm status.
To stop a zone Alarm (Events
1
through
160
) or partition Alarm (Events
161
through
208
)----use a valid digital key
at a key reader that is enabled on the partition/s in alarm status.
For example, this will stop the outputs connected to Sirens, but will not clear the call queue.
To stop outputs and clear the call queue----by digital key----program as follows.
Introduction
Ø
Event no. 255:
Valid key on partition 1
Ø
Output no. 4:
refers to terminal [OC2] of the Main unit
Ø
Zone no. 6:
refers to terminal [L6] of the Main unit
Connect as per figure 51 and refer to the following programming instructions (divided into programming pages).
Event-Actions
Program
event no. 255
----Valid key on partition1----as follows:
Ø
Outputs ON:
4
Outputs
Program
output no. 4
as follows:
Ø
Type:
Monostable
Ø
Attributes:
Normally closed
Ø
Time:
On Time 1 Sec.
Zones
Program
Zone no. 6
as follows:
Ø
Command:
Clear call queue
Ø
Balancing:
Normally closed
Ø
Sensitivity:
Standard
Digital keys (enabled on the partitions in alarm status) will clear the call queue and stop all the Alarm events----
when inserted into a key reader that is enabled on the same partitions.
+
If alarm conditions persist, after extraction of the digital key----Alarm status signalling will restart as per program-
ming (output activation, telephone calls, etc.).
+
Valid digital keys
can stop
zone and partition alarm events but
cannot
stop
Panel alarm events unless the
Stop
alarm by digital key
option is enabled.
+
If both partition and control panel alarms activate the same output, that is,
Generic alarm on partition no.
and
Generic alarm on panel
and both alarms are active----the digital key will stop the
Generic alarm on partition no.
event but not the
Generic alarm on panel
event, therefore, the output (e.g. Siren) will not be stopped.
+
These solutions will stop the alarm events and assigned outputs but will not delete the alarm memory. To do
this----use the Alarm reset command from the keypads USER MENU. However, the alarm memory will be deleted
automatically, when the partitions are next armed.
L6
Main unit
Output n. 4:
Monostable
Normally closed
On time - 1 Sec.
Zone n. 6:
Command
Clear call queue
Normally closed
Pulses - 1
Figure 51
Stop Alarm by digital key
APPLICATIONS
79