Several outputs assigned to the same event
Sometimes----especially in noisy places----zone alarm signalling requires sirens and flashers----placed in strategic
positions. For this purpose, several outputs can be assigned to the same event----and the event will activate the
assigned outputs on the BPI bus.
If output OCx is assigned to an event, and the same event must activate signalling on outputs OC1, OC2, OC3, ...,
OCn----make the connections illustrated in figure 45, and program as per below.
+
Output OCx and inputs L1, L2, L3, ..., Ln should be close together for connection purposes.
Zones
Program the zones that correspond to terminals [L1], [L2], [L3], ..., [Ln] as follows:
Ø
Alarm
Ø
Type:
24h
Ø
Balancing
compatible with the attribute of output OCx:
- Normally open
if the output OCx is normally open
- Normally closed
if the output OCx is normally closed
Ø
Partition:
all the zones should be assigned to a partition that is not used by keys, codes or to control operations----this
partition can be considered a Technical partition.
Outputs
The output that corresponds to terminal [OCx] can be programmed as per requirements, while the outputs that cor-
respond to terminals [OC1], [OC2], [OC3], ..., [OCn] should be programmed as follows:
Ø
Type:
Bistable
Event-Actions
Program the
Zone alarm events
of terminals [L1], [L2], [L3], ..., [Ln] as follows:
Outputs ON
Ø
Alarm on zone (L1):
Output (OC1)
Ø
Alarm on zone (L2):
Output (OC2)
Ø
Alarm on zone (L3):
Output (OC3)
Ø
Alarm on zone (Ln):
Output (OCn)
Connections and programming done----activation of output (OCx) will generate the following events:
24h alarm on
panel
,
Generic alarm on panel
and
Tamper alarm on panel
. To avoid false alarms----these events
must not be assigned to actions.
As a result of the described connections and programming, the signal on output OCx will also be present on out-
puts OC1, OC2, OC3, ..., OCn with a 2 second delay (approx.).
+
The signal on output OCx must be present for more than 400 mS in order to activate outputs OC1, OC2, OC3, ...,
OCn.
Zones (L1, L2, L3, .., Ln):
Alarm
24h
Normally open
(Normally closed)
Sensitivity - Standard
Pulses - 1
Output (OCx):
Normally open
(Normally closed)
Alarm on zone (L1)
è
Alarm on zone (L2)
è
Alarm on zone (L3)
è
Alarm on zone (Ln)
è
Event-Actions
Output (OC1)
Output (OC2)
Output (OC3)
Output (OCn)
Outputs (OC1, OC2, OC3, .., OCn):
Bistable
Figure 45
Multiple output event
72
Expandable Multifunction Control Panel