Function
29
FTC470XDP_D00111_00_M_XXEN/02.2015
6.3.2
Requesting alarm messages via the channel number
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.3: Master request: requests for alarm messages or information via channel number
Reading from FTC470XDP (= input data of the PROFIBUS Master):
Function
Devices
Channel
No.
BMS
command
Data
Type
Data
Value
Requests for alarm messages or information via
channel number
all
Channel
No.
2
0
0
No alarm
all
Channel
No.
2
1
0
Insulation fault in the IT system
MK2418-11
SMI470-9
1
1
2
11
1
Transformer overload
MK2418-11
SMI470-9
2
2
2
11
2
Transformer overtemperature
107TD47
IZ427
MK2418-11
SMI470-9
3
3
3
3
2
11
3
Failure line 1
PRC487
MK2418-11
SMI470-9
1
4
4
2
11
4
Failure line 2
PRC487
MK2418-11
SMI470-9
2
5
5
2
11
5
Insulation fault operating theatre lamp
107TD47
MK2418-11
SMI470-9
8
6
6
2
11
6
Failure distribution board (Line 3, upstream the
switchover device)
PRC487
MK2418-11
SMI470-9
3
8
8
2
11
8
Failure AV line
PRC487
1, 2
2
11
25
Failure SV line
PRC487
1, 2
2
11
26
Failure UPS line
PRC487
1, 2
2
11
27
Failure N conductor
PRC487
4
2
11
29
Short circuit distribution board
PRC487
10
2
11
30
Phase sequence left
ATiCS
30
2
11
39
Failure BSV line
(Battery-backed power supply system)
ATiCS
1, 2
2
11
40
Connection fault system
107TD47
IRDH…
4
3
2
12
101
Connection fault PE
107TD47
IRDH…
IZ427
5
4
5
2
12
102
Short circuit CT input
107TD47
IZ427
EDS46x/49x
RCMS460
RCMS490
6
6
1…12
1…12
1…12
2
12
103
Содержание FTC470XDP
Страница 10: ...Safety instructions 10 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 22: ...The FTC470XDP protocol converter 22 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 26: ...Installation 26 FTC470XDP_D00111_00_M_XXEN 02 2015...
Страница 79: ......