Function
40
FTC470XDP_D00111_00_M_XXEN/02.2015
Table 6.17: Master request: setting the response values
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.18: FTC reply to: setting the response values
* The read-out data type corresponds to the previously defined data type.
** Example SMO482-12 (table 6.17)
An A-Isometer with BMS address 3 provides an alarm message on channel 2. An SMO482-12 with ad-
dress 37 located in the BMS network must signal this alarm message at its output
relay 1. Output relay 1 = channel number 1 of SMO482-12. Which data value must be entered?
SMO address = 37
SMO channel no. = 1
ISOMETER address = 3
ISOMETER channel no. = 2
Data value = 3 x 100 + 2 = 302
Data value to be entered = 302
LSD470 mode
Display language
EDS mode
107TD47
16
17
18
28
181
"
Response value insulation monitoring in k
Ω
107TD47
5
28
182
"
Response value load current in A
107TD47
6
28
183
"
Time delay of the alarm relay in s
107TD47
7
28
184
"
Acknowledgement
RCMS…
chan-
nel No
28
*
value
Invalid value
RCMS…
"
28
255
255
Data value = alarm address x 100 + channel
no. (of the alarm giving device)
SMO482-12
37
1
28
96
302
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value