Programming examples
61
FTC470XDP_D00111_00_M_XXEN/02.2015
The PROFIBUS Master addresses BMS address 29, 107TD47, for information about the actual load of
the transformer (operating message). This value is available at channel 2 of the
device:
PROFIBUS Master output data:
The 107TD47 replies that the transformer utility is 66 % :
PROFIBUS Master input data:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
9
0
29
2
4
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
9
0
29
2
4
65
0
66