Function
47
FTC470XDP_D00111_00_M_XXEN/02.2015
6.7.15 Requesting the channel function
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.43: Master request: request for a channel’s function
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.44: FTC reply to: request for a channel’s function
6.7.16 Setting the channel function
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.45: Master request: setting the channel’s function
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.46: FTC reply to: setting the channel ’s function
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for the current function of a channel
all
channel
No.
39
1
0
Overcurrent monitoring, residual current monitoring
RCMS…
1… 12
39
1
1
Undercurrent monitoring, open circuit
RCMS…
1… 12
39
1
2
Input switched off
RCMS…
1… 12
39
1
3
Alarm address ON
MK2418
1… 30
39
1
4
Alarm address OFF
MK2418
1… 30
39
1
5
No more channels
all
channel
No.
39
254
254
Invalid value
all
channel
No.
39
255
255
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Setting the channel to overcurrent/
residual current monitoring
RCMS…
1… 12
38
1
1
Setting the channel to undercurrent / open circuit
monitoring
RCMS…
1… 12
38
1
2
Switching the channel function off
RCMS…
1… 12
38
1
3
Setting the alarm address to ON
MK2418
1… 30
38
1
4
Setting the alarm address to OFF
MK2418
1… 30
38
1
5
Acknowledgement
RCMS…,
MK2418
1… 12
38
1
value
Invalid value
"
channel
No.
38
255
255
Содержание FTC470XDP