![Beluk BLR-Q(U) I/O Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/beluk/blr-q-u-i-o/blr-q-u-i-o_reference-manual_2730834038.webp)
Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 38 of 39
6 Technical Data
Auxiliary voltage
100 - 132V / 207 - 253V, 45-65Hz, max. fuse 6A
Voltage measuring
50 – 530V, 45 – 65Hz, PT-ratio 1 - 350
Current measuring
0 – 5A, sensitivity 15mA, burden 15mΩ (option -3A: 3x 0 – 5A)
overload 20% continuous, CT-ratio 1 - 6500
Control exits
6R, 12R, 6T, 12T, 12RT
relays: N/O, one common point, max. fuse 6A
breaking capacity:
250V AC / 5A, 400V AC / 2A, 110V DC / 0,4A, 30V DC / 5A
static outputs: open-collector, breaking capacity: 8 – 48V DC / 100mA
Alarm contact
C/O, voltfree, programmable
max. fuse 6A, breaking capacity 250V AC / 5A
Digital input DI0.1-DI0.2
(optional)
10 – 30V DC, for synchronization of data-logger
Digital input DI1.1-DI1.2
50 – 250V AC, programmable
Digital output
N/O, voltfree, programmable
max. fuse 6A, breaking capacity 250V AC / 5A
Data-logger (optional)
2MB
Interface (optional)
RS485 Modbus RTU protocol (Slave)
Ambient temperature
operation: 0°C ... +70°C, storage: -20°C ... +85°C
Humidity
0% - 95%, without moisture condensation
Overvoltage class
II, pollution degree 3 (DIN VDE 0110, Teil 1 / IEC 60664-1)
Standards
DIN VDE 0110 Teil 1 (IEC 60664-1:1992)
VDE 0411 Teil 1 (DIN EN 61010-1 / IEC 61010-1:2001)
VDE 0843 Teil 20 (DIN EN 61326 / IEC 61326:1997 + A1:1998 + A2:2000)
Conformity and listing
CE, UL, cUL, GOST-R
Terminals
screw-type, plugable, max. 2,5mm
2
Casing
front: instrument casing plastic (UL94-VO), rear: metal
Protection class
front: IP 54, rear: IP 20
Weight
ca. 0,8 kg
Dimensions
144 x 144 x 58mm (h x w x d), cutout 138
+0,5
x 138
+0,5
mm