Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 11 of 39
2.3.2 SWITCH CYCLES
BLR-Q(U) is counting and showing the switching cycles of each step. This value allows the conclusion about
the actual state of the contactors. Switch cycles can be preset separately for each step in SETUP/STEPS
(2.4.22.3). Switch cycles of all steps is also reset, by a reset of complete capacitor database in
SETUP/RESET (2.4.28.3).
2.3.3 STEPVALUE
As standard, the STEPVALUES are detected automatically during operation. They are rated to the setting of
nominal voltage. In some special applications, it is required to set the step values manually. This can be
done in SETUP/STEPS (2.4.22.4).
The STEPVALUE is showing the size of the capacitor, which is used for reactive power regulation. The func-
tion of this value can be compared with the c/k value of power-factor control relays of former generations.
The STEPVALUE is shown in kvar. Each step has its own STEPVALUES, at BLR-Q(U) it’s one per step.
Step database is working with two values of capacitor size. The value which is shown in kvar is the actual
value. This is continuously corrected with every switching operation. A second value is saved after the first
ten switch cycles of each step after a reset of step database. This value indicated the original available
STEPVALUE. This value is used to calculate the percentage of actual stepvalue to original stepvalue. This
percentage gives very simple information about derating of the capacitor banks.
2.3.3.1
When automatic step recognition is not active, the percentage is not shown (2.4.23.5).
2.4 Quickstart SETUP
In this submenu basic settings can be made for the BLR-Q(U). These settings are neces-
sary for correct function and for correct display of the measurement values. This menu can
be entered without password.
The following parameters can be set in Quickstart menu:
2.4.1 CHANGE LANGUAGE
Standard version of BLR-Q(U) is supporting English, German and French.
2.4.2 NOMINAL VOLTAGE
Function of the setting of nominal voltage is to make a definition about the nominal voltage of the system.
This nominal voltage is valid for normal control mode and voltage control mode. The threshold levels for
under- and overvoltage are based on this as well as the ratings of the capacitor sizes in step database,
which are used for control and monitoring (0 and 2.4.21.8). The capacitor sizes, which are stored in step
database, are also rated to the nominal voltage.
Independent of connection of the voltage measuring channel, nominal voltage is always the
phase-phase voltage
!
!