![Beluk BLR-Q(U) I/O Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/beluk/blr-q-u-i-o/blr-q-u-i-o_reference-manual_2730834035.webp)
Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 35 of 39
4 Standard Setting
Function
Factory setting
Range of setting
Customer setting
Language
English
English, German, French
CT-factor
1
1,0 – 6500,0
VT-factor
1
1,0 – 350,0
Nominal voltage (ph-ph)
400V
100 – 220000V
Connection measurement
L-N
L-N, L-L
Synchronisation frequency
Auto
Auto, 50Hz or 60Hz
Phase compensation
0°
0° … 345°, steps 15°
V-tolerance min
10%
2 – 90%
V-tolerance max
10%
2 – 30%
Countdown Start AI
yes
yes / no
Temperature offset
0 °C
-10 to + 10 °C
CT type 1A
no
yes / no
Discharge time
75s
0,1s – 1200,0s
Step type
normal
normal, fix on, fix off, off,fast
Control
on
on / freeze / off
Cos phi 1
1.00
0,60 i – 1,00 – 0,70c
Cos phi 2
i 0,95
0,60 I – 1,00 – 0,70c
Switch interval
10s
1,0s – 1200,0s
Switch interval step exchange
2s
1,0s – 1200,0s
Asymmetry factor
1
-127 to +127
Step recognition
on
on / off
Switch cycle balancing
no
yes / no
Switch cycle balancing %
10%
1% - 15%
Step exchange
yes
yes / no
Control sensitivity
60%
55% - 100%
Control
Auto
Auto / LIFO / progressive/ combi filter
Q Offset
0 kvar
-+ 3200 kvar
I < limit freeze steps
no
yes / no
Q cap. steps turn off
no
yes / no
Fast meas delay
50 periods
0 –900 periods
Fast max step value
0 kvar
0 – 9999,9 kvar
Fast meas mean
0 periods
0 – 900 periods
Control alarm
M, D
disabled, M, DO, D, CP, O, F
No current alarm
M
disabled, M, DO, D, CP, O, F
Step fault
M, D
disabled, M, DO, D, CP, O, F
Step warning
M, D
disabled, M, DO, D, CP, O, F
Limit step warning
50%
15 – 80%
Limit switch cycles
100000
1 - 9999999
Cos phi alarm
disabled
disabled, M, DO, D, CP, O, F
Limit cos phi min
c 0.90
c 0.90 – limit max - 0,01
Limit cos phi max
i 0.90
i 0.90 – limit min – 0.01
∆
T (time delay)
300s
1s – 36000s
Harmonic U alarm
M, D
disabled, M, DO, D, CP, O, F
Limit harmonics U
20%
1% - 99,9%
Harmonic I alarm
disabled
disabled, M, DO, D, CP, O, F
Limit harmonics I
50%
1% - 99,9%
Alarm overload P
no
disabled, M, DO, D, CP, O, F
Limit overload P
1.00kW
1.0 ... 99999.9 kW
Alarm overload Q
disabled
disabled, M, DO, D, CP, O, F
Limit overload Q
1.00kvar
1.0 ... 99999.9 kvar