Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 30 of 39
2.6 DATALOGGER (option –DM)
2.6.1 SETUP-HISTORY
Setup history gives infromation about the last 64 settings. It is working as ring-buffer, so the oldest informa-
tion is overwritten.
Setup history gives information about date and time and type of paramter which is changed. By pushing the
◄►-key, you can change to the values. On top line you can see the actual value the bottom line shows the
former value of the modified parameter.
2.6.2 ALARM-HISTORY
Alarm history gives information about the last 64 alarm states. It is working as ring-buffer, so the oldest in-
formation is overwritten. It shows release and reset of alarms.
Alarm history gives information about date and time and type of alarm.
By pushing the ►-key, you can see the reason of the alarm. On top line you can see the value in the
moment when alarm comes, the bottom line shows the threshold level of alarm.
By pushing the ►-key again, you get informations about the current and voltage in the moment of alarm.
2.6.3 Logging of measurings
BLR-Q(U) can log upto 3072 sets of measurings with date and time. The interval can be set from 1 minute to
720 minutes (0=stop logging). Alternatively, there can be use the digital input (
Fehler! Verweisquelle konn-
te nicht gefunden werden.
) of data-logger to synchronize the log-interval to other applications. It is working
as ring-buffer, so the oldest information is overwritten.
To download logged measurings, please use TTL interface and software “Data_log”.
Data can be stored as CSV – file. For analysis of data you can use common available spreatsheet software.
2.6.4 Logging of system information
BLR-Q(U) can log upto 512 sets of system information with date and time (enough for 1,4 years). It is work-
ing as ring-buffer, so the oldest information is overwritten. This log happens every day at 23:59:59.
System information are: kWh, kvarh, number of switching operations per exit, capacitor size, average PF,
average PF of last 24h. This logging is always active.
To download logged information, please use TTL interface and software “Data_log”.
Data can be stored as CSV – file. For analysis of data you can use common available spreatsheet software.
2.7 DEVICE INFO
Device type:
e.g BLR-Q(U)
Softwareversion
: e.g. VER 02.07.00
FLG
: e.g. 3I MB DL