Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 28 of 39
2.4.26 MODBUS
This submenu is only enabled when the regulator is equipped with the Modbus interface. The following set-
tings are possible:
•
BAUD RATE
: The baud rate can be selected by pushing the ◄►-key. The valid range is between
1200 and 38400.
•
PARITY
: The parity can be selected by pushing the ◄►-key. The following settings are possible:
8E1 (8 data bits/even parity/1 stop bit), 8O1 (8 data bits/odd parity/1 stop bit) and 8N2 (8 data bits/no
parity/2 stop bits)
•
ADDRESS
: By pushing the ►-key it is possible to enter the slave address (slave ID). The valid
range is between 1 and 247.
The settings for baud rate and parity must be the same for all bus devices. The address must be unique for
each device.
2.4.27 DATALOGGER
This submenue is only avaialble when the regulator is equipped with datalogger. To use datalogger, some
settings are required. These settings are: date, time, storage interval, synchronisation to digital input and
trigger of digital input.
2.4.27.1 Date and time
Format of date: dd-mm-yy
Format of time: hh:mm (seconds are running in a separate line)
2.4.27.2 STORAGE INTERVAL
The storage interval can be set from 1 to 720 minutes.
A setting of 0 stops datalogging of measuring values.
2.4.27.3 SYNCHRONISATION
The storage interval can be synchronized to other devices. This happens by a trigger signal to digital input
DI0.1/DI0.2 (
Fehler! Verweisquelle konnte nicht gefunden werden.
). To use the synchronization, it is
required to select the correct storage interval. The tolerance is 20 sec. When within the time of storage inter-
val + 20 sec BLR-Q(U) cannot detect a trigger signal, it will give a failure message. If the trigger signal
comes earlier as the end of interval, then the interval is finished with trigger signal.
2.4.27.4 SETUP DI Input
The digital input can be triggered to two conditions:
-
HIGH: rising edge
-
LOW: falling edge