Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 29 of 39
2.4.28 RESET
2.4.28.1 RESET SETUP
Reset of BLR-Q(U) to factory settings without step database.
2.4.28.2 RESET FAULTY STEPS
Reset of steps, which are detected as faulty, back to automatic mode.
2.4.28.3 RESET STEPS
Reset of step database. This affects the following values: steptyp, stepsize, switch cycles, discharge time.
2.4.28.4 RESET WORK COUNTER
Reset of KWh and kvarh counters.
2.4.28.5 RESET OPH
There is a possibility to change the setting for operation hours or to set them to zero.
2.4.28.6 RESET APF
Reset of average PF.
2.4.28.7 RESET T-MAX
Reset of the temperature maximum, which was measured.
2.4.28.8 DATALOGGER DELETE
Deletes all saved values in datalogger.
2.5 MANUAL
To enter in manual mode, please select “manual” in main menue and push ► for 3 seconds. The automatic
control is stopped and the exits can be switched manually. By the means of the
+
-key the referring step can
be selected. Changing the switching state is possible by pushing the ◄►-key.
Manual switching is only possible when measurement voltage is in allowed range. Other-
wise over- and undervoltage protection will block this function. After switching off an
active step the discharging time is active. Only after this time is over the step can be
switched on manually again.
Difference to versions before 2.7.0:
-
during the manual mode the automatic control is stopped
-
when you are leaving manual mode, the connected steps will be not disconnected
-
the test-mode which allows switching capacitors when voltage and current are out of range is removed
!